Supply Voltage |
110VAC 50/60Hz, 220VAC 50/60Hz, 24VDC |
Operating Voltage Range |
90 to 110% of rated voltage |
Power Consumption |
12 WATTS(max), 9W(steady state) |
Input |
4-20mA or RTD |
Output |
4-20mA standard, ¡¾5% span accuracy |
Control Action |
Direct or Reverse |
Control method |
P, PI, PID. |
Local Set Point Adjustment |
Push Button Switches and Digital Display |
Remote Set Point Adjustment |
4-20mA Standard Input |
Display Modes |
Process Value(PV), Set Point(SP), |
Communication |
Deviation(DEV)=Process Value-Set Point,
Various Parameters such as Max, Min, unit
Approaching Various Parameters and Displaying
its Result By Using RS 232C
|
Troubleshooting |
Service zMode, LED Display For Error |
Air supply |
100psi Max |
Air Output |
Zero To Maximum Supply Pressure |
Air Consumption |
Zero At Steady State Conditions |
Accuracy |
¡¾0.5% Of Full Span |
Input Resistance To Current Loop |
100 §Ù ¡¿ Currency + 0.7V |
Ambient Temperature Rating |
-30 to 60¡ÆC |
Dimensions |
205(width)¡¿260(depth)¡¿130(height)mm |
Enciosure |
MEMA 4/4 ¡¿ Polycarbonate |