| Supply Voltage |
110VAC 50/60Hz, 220VAC 50/60Hz, 24VDC |
| Operating Voltage Range |
90 to 110% of rated voltage |
| Power Consumption |
12 WATTS(max), 9W(steady state) |
| Input |
4-20mA or RTD |
| Output |
4-20mA standard, ¡¾5% span accuracy |
| Control Action |
Direct or Reverse |
| Control method |
P, PI, PID. |
| Local Set Point Adjustment |
Push Button Switches and Digital Display |
| Remote Set Point Adjustment |
4-20mA Standard Input |
| Display Modes |
Process Value(PV), Set Point(SP), |
| Communication |
Deviation(DEV)=Process Value-Set Point,
Various Parameters such as Max, Min, unit
Approaching Various Parameters and Displaying
its Result By Using RS 232C
|
| Troubleshooting |
Service zMode, LED Display For Error |
| Air supply |
100psi Max |
| Air Output |
Zero To Maximum Supply Pressure |
| Air Consumption |
Zero At Steady State Conditions |
| Accuracy |
¡¾0.5% Of Full Span |
| Input Resistance To Current Loop |
100 §Ù ¡¿ Currency + 0.7V |
| Ambient Temperature Rating |
-30 to 60¡ÆC |
| Dimensions |
205(width)¡¿260(depth)¡¿130(height)mm |
| Enciosure |
MEMA 4/4 ¡¿ Polycarbonate |